Gas Accumulation Indicator, Qualitrol Corp 038 Series
Provides Continuous Indication Of The Total Accumulated Gases; Spdt Switch Provides A Latching Alarm When The Accumulated Gas Displaces A Greater Volume Of Oil Than The Switch Set Point; 6 Inch (152.5Mm) Dial Face Is Set At 15? Angle To Be Easily Viewed From The Base Of The Transformer Or Related Apparatus; Provides Continuous Indication Of The Total Accumulated Gases; An Spdt Switch Built Into The Gage Case Actuates When The Accumulated Gas Displaces Greater Than 200Cc Of Oil, Triggering A Latching Alarm That Will Remain On Until Sufficient Gas Is Removed; Gas Can Be Drawn Off From The Accumulator For Analysis Via The Integrated Sampling Port; Optional ?Sampling Valve Kit? (Vlv-602-1) Allows The Samples To Be Drawn Off More Easily At The Bottom Of The Tank; Optional ?Sampling Syringe Kit? (Kit-005-1) Provides Useful Tools And Hardware To Take Measured Samples Of Gas; Aluminum Case And Flange Are Finished With A Thermosetting Powder-Coat; Stainless Steel Hardware, Cup And Bezel And Uv Stabilized Polycarbonate Lens For Maximum Durability; Dial Face Is Set At A 15? Angle For Easy View From The Base Of The Transformer; Large 6_ (152.5 Mm) Dial Face Can Be Customized To Maximize Readability For The Application
Description
Mechanical measurement of gas accumulation within a conservator style transformer. Alarm functions warn when level hits maximum limit and remains on until sufficient gas is removed. Sampling port allows your personnel to draw-off of gas for laboratory analysis.
Additional information
Series | 042 |
---|---|
Options | Cable Type, Color And Length |
Applications | For use on conservator style transformers to indicate and alarm when undesired gases, have been detected and have accumulated in volume past an alarm set point., typically a result of internal arcing |
Do you have questions? We have answers.
Call us at 769-235-6665, or click the button to send us a message.